Number of analogue outputs
|
2
|
Mains voltage
|
480 V
|
Integrated breaking resistance
|
No
|
Max. output voltage
|
932 V
|
Internal dynamic brake resistors
|
115 Ohm
|
DC bus overvoltage trip
|
810V DC @ 480V
|
DC nominal bus voltage
|
648V DC @ 480V
|
Brake IGBT
|
Brake IGBT installed
|
Internal communication module
|
No communication module
|
Fuse current rating
|
40 A @ 650V DC
|
Input voltage rating
|
480V AC, 3-phase, 60 Hz
|
Displacement power factor
|
0.98 across speed range
|
Output current, continuous
|
22 A @ 650V DC
|
Output current, 1 min
|
24.2 A @ 650V DC
|
Output current, 3 sec
|
33 A @ 650V DC
|
Circuit breaker current rating, max
|
80 A @ 480V AC, 3-phase
|
Motor circuit protector current rating, max
|
30 A @ 480V AC, 3-phase
|
Logic control ride-thru
|
0.25 seconds, drive not running
|
Brake resistor
|
No internal brake resistor
|
Input current rating
|
23.3 A @ 650V DC
|
Rated power rating
|
15 Hp @ 650V DC, normal duty
|
Documentation
|
English documentation
|
Carrier frequency
|
Drive rating: 4 kHz, settings: 2, 4, 6, 8, 10 kHz (6 kHz is for V/Hz operation only)
|
AC input overvoltage trip
|
600V AC @ 480V (six pulse, 3-phase)
|
Input power rating
|
16.6 kVA @ 480V AC, 3-phase
|
Electronic motor overload protection
|
Class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A)(2). UL 508C file E59272
|
Dual element time delay fuse current rating
|
25...50 A @ 480V AC, 3-phase
|
Non-time delay fuse current rating
|
25...80 A @ 480V AC, 3-phase
|
Heat sink thermistor
|
Monitored by microprocessor overtemperature trip
|
Drive to motor power ratio, max
|
The drive to motor rating cannot exceed a 2:1 ratio
|
Stop modes
|
Multiple programmable stop modes including – Ramp, Coast, and Current Limit
|
Acceleration/deceleration
|
Independently programmable accel and decel times adjustable from 0 to 6553.5 in 0.1 second increments
|
Number of digital inputs
|
6
|
Number of digital outputs
|
2
|
Number of analogue inputs
|
3
|
Motor voltage, nom
|
460V @ 380...400V drive rating, 480V nominal line voltage
|
Human interface model
|
No HIM (no blank plastic inserted)
|
Additional configuration
|
Phase II control
|
Max. output frequency
|
400 Hz
|
Line voltage, nom
|
480V @ 380...400V drive rating, 460V nominal motor voltage
|
Mains frequency
|
60 Hz
|
Internal EMC filtering
|
With EMC filter & common mode choke
|
Watt loss
|
389 W @ 480V AC, 15 Hp normal duty, 10 Hp heavy duty
|
Feedback option
|
Future use
|
Drive full power range
|
460...528V @ 380...400V drive rating, 460V nominal motor voltage
|
Drive operating range
|
325...528V @ 380...400V drive rating, 460V nominal motor voltage
|
Torque regulation
|
Torque regulation - without feedback: ±5%, 600 rad/sec bandwidth
|
Enclosure type
|
IP20/NEMA/UL Type 1
|
Output current rating
|
22 amps, 15 Hp normal duty, 10 Hp heavy duty, frame 1
|
Control options
|
Phase II control, expanded cassette
|
Drive overcurrent trip
|
Software current limit: 105% of motor rated to 200% of drive rated current
|
Efficiency
|
97.5% at rated amps, nominal line volts
|
Speed control
|
Speed regulation - without feedback: 0.1% of base speed across 120:1 speed range, 120:1 operating range, 50 rad/sec bandwidth
|
Current limit capability
|
Independent motoring and regenerative power limits programmable to 800% of rated output current
|
Selectable motor control
|
Field oriented control with and without a feedback device and permanent magnet motor control
|
Input phases
|
Six-pulse, 3-phase input provides full rating for all drives, single-phase operation provides 50% of rated current
|
Control method
|
Induction motor and brushless motor: sine coded PWM with programmable carrier frequency, indirect self organized, field-oriented control, current-regulated, ratings apply to all drives, refer to the PowerFlex 700S Phase ll control reference manual, public
|
Number of phases output
|
3
|
Number of phases input
|
3
|
Relative symmetric net voltage tolerance
|
10 %
|
Input frequency, max
|
400 Hz
|
Output frequency range
|
0 Hz
|
DC bus undervoltage trip
|
Adjustable
|
Output voltage range
|
0 to rated motor voltage
|
Power ride-thru
|
15 milliseconds at full load
|
S-curve time
|
Adjustable 0.5...4.0 seconds
|
Short circuit trip
|
Phase-to-phase on drive output
|
Ground fault trip
|
Phase-to-ground on drive output
|
Control logic noise immunity
|
Showering arc transients upto 1500V peak
|
Line transients
|
Up to 6000 volts peak per IEEE C62.41-1991
|
Intermittent overload
|
110% overload capability for up to 1 minute, 150% overload capability for up to 3 seconds
|
Short circuit current, max
|
Using recommended fuse or circuit breaker type: maximum short circuit current rating to match specified fuse/circuit breaker capability ≤200000 Amps
|
Encoder voltage supply
|
5V DC or 12V DC 320 mA/channel, 5V DC minimum high state voltage state of 0.4V DC, 12V DC minimum high state voltage of 7.0V DC, maximum low state voltage of 0.4V DC
|